Pre-action sprinkler systems

A sprinkler grid that stays dry until detection and a head both agree there is a fire. For rooms where an accidental discharge would cost more than the fire.

A fire pump room: red hydrant pump and jockey pump, control panels and painted steel pipework running to the ceiling.
Kgbo · CC BY-SA 4.0
Scope
Survey → commissioning → AMC
Practice
IS 15105 · NBC 2016 Pt.4
Typical use
Data halls, archives, museums
What it is

Two things have to happen before any water moves

In an ordinary wet system the pipework above the ceiling is full of water at all times, and a knocked-off head empties it onto whatever is below. A pre-action system holds that water back at a valve in the plant room and keeps the grid dry. Detection in the room opens the valve; the sprinkler head still has to reach its own temperature before anything discharges.

That double interlock is the whole point. A damaged head on a dry grid releases air, not water — the panel reports a low-air fault and someone goes and looks. It is the arrangement for rooms where the contents are the reason the building exists: data halls, record rooms, control rooms, museum stores and switchgear rooms.

The design is a sprinkler design plus a detection design, and the two have to be commissioned together. We prove the releasing sequence end to end — detector to panel to solenoid to valve — with the grid isolated, then again with air pressure restored, and hand over the cause-and-effect matrix that the release logic was set against.

Equipment

What the installation is built from

A pre-action installation is a sprinkler grid, a detection system and a releasing valve that only opens when both say so.

Pre-action valve assemblyThe valve that holds the water at the plant room, with its trim, gauges and manual release.
Releasing control panelRuns the interlock, supervises the solenoid and the air line, and reports every state to the main fire panel.
Detection over the protected areaSmoke or heat detection on its own loop, laid out to see the fire before a head would.
Solenoid and manual releaseThe electrical trip, and the mechanical one for a person standing at the valve.
Air compressor and supervisory airHolds the grid at pressure so a leak or a damaged head is reported as a fault rather than discovered as a flood.
Low-air and valve-status supervisionSwitches on the valve and the air line, so an isolated or drained system cannot sit unnoticed.
Dry pendant and upright headsRated per area, on a grid pitched and drained so no water is left standing after a test.
Test, drain and air-vent pointsWhat makes the system provable on a service visit without emptying it over the room.